§ 171.087 LIGHT AND VENTILATION.
   (A)   Kitchenettes, bathrooms and toilet rooms shall be provided with artificial light appropriate for the use of such rooms.
   (B)   Laundry rooms, furnace rooms and similar non-habitable space shall be provided with artificial light appropriate for the intended use of such rooms.
   (C)   Stairs shall be provided with artificial light to allow safe ascent or descent.
   (D)   Kitchenettes, bathrooms and toilet rooms shall be provided with ventilation in accordance with either of the following:
      (1)   Natural ventilation as required for habitable space; except that, such openable areas shall be not less than one and one-half square feet for bathrooms or toilet rooms and not less than three square feet for kitchenettes; or
      (2)   Mechanical ventilation exhausting not less than 25 cubic feet per minute for bathrooms and toilet rooms and not less than 100 cubic feet per minute for kitchenettes.
   (E)   Spaces in multiple dwellings which contain central heat producing, air conditioning and other equipment shall be ventilated to the outer air, and air from these spaces shall not be recirculated to other parts of the building.
   (F)   Ventilation shall be provided in unheated attics, spaces below flat roofs and crawl spaces. Location and net areas of ventilation openings shall be such as to minimize deterioration of structural members from condensation or other causes, in conformity with generally accepted standards.
(Prior Code, § 19-88) (Ord. 312, passed 3-25-1963) Penalty, see § 171.999