1505.04 REQUIREMENTS.
   (a)   No smoke detector and carbon monoxide detector shall satisfy the requirements of Section 1505.02 unless it shall bear the label of a nationally recognized testing laboratory.
   (b)   No smoke detector shall be used unless it is sensitive to both visible and invisible products of combustion. Smoke detectors sensitive to heat only are not acceptable.
   (c)   No detector shall be used which does not contain an alarm-sounding device rated at a minimum of 85 decibels at ten feet and is audible to sound this level of warning for a minimum of four continuous minutes and, in addition, be clearly audible in all bedrooms within a dwelling when all intervening doors are closed.