1345.06 CONSTRUCTION.
   (a)   Only corrosion-resistant material shall be permitted in the support structure.
   (b)   The structure and installation shall be in conformance with Article 810 of the National Electrical Code.
   (c)   Only a concrete base or caissons, depending upon soil conditions, extending not less than three and one-half feet below the surface, except where the same is on rock or when specifically permitted by the Building Inspector, shall be employed in line with the grade.
   (d)   The maximum height of any free-standing satellite (free-standing earth station) or disc antenna shall be twenty feet from the natural grade level. No antenna shall exceed a height of sixty feet.
   (e)   The structure, including the foundation, shall be designed to withstand a wind velocity or force of eighty-five miles per hour in accordance with generally accepted engineering practice.
   (f)   All underground electrical wiring shall be U.L. approved with an eighteen-inch cover. Grounding shall conform to Article 250 of the National Electrical Code.
   (g)   Any driving motor shall be limited to 110V maximum power design and be encased in protective guards.
   (h)   If guy wires are used, they shall be confined within a fenced area or protected by suitable shields.
   (i)   The requirements of this section may be modified in industrial, commercial or multifamily districts, if the Building Inspector, after reviewing the plan and any other information requested, finds that such erection or installation is consistent with sound engineering practice.
(Ord. 93-32. Passed 4-5-94.)