755.08 SAFETY DEVICES.
   (a)   All tanks for the storage of flammable liquid used in conjunction with self-service dispensing devices shall meet the requirements of this Code for flammable liquid tanks. Automatic hose nozzle valves with latch open devices are prohibited.
   (b)   All pipes supplying flammable liquids to approved self-service dispensing devices shall be equipped with electrically operated shutoff valves. All controls to such valves shall be in a centrally located area remote from all dispensing devices and adequately protected from the weather and mechanical injury. The valves shall be so designed as to close automatically in case of electrical power failure. All electrical equipment shall be listed for use in such areas.
   (c)   Every self-service station shall be provided with a minimum of one approved fire extinguisher listed for use in Class B fires, rated 60BC or larger and one additional extinguisher of the same type for each island. The fire extinguisher shall be visible within fifty feet and shall be in place during all hours the station is in operation. Extinguishers shall be protected from weather and mechanical injury.
   (d)   Warning signs prohibiting smoking and instructing customers to turn off ignition systems during filling operation shall be posted in a conspicuous location at each island. Such signs shall have a white background with the words “No Smoking” and “Turn Off Engine” in red letters, a minimum of four inches high and with a minimum of a one-half inch stroke. Signs with directions for operation of the dispensing devices shall also be provided.
(Ord. 1983-40. Passed 5-17-83.)