1560.04 LOCATION AND STORAGE.
   Location and storage shall be outside of a building for containers awaiting use or resale. Containers shall be located in accordance with Ohio Fire Code FM-36-4.1 and NFPA standard #58 and shall be at least ten feet from any doorway or five feet from any opening (windows, vents, etc.) into a building frequented by the public. No propane tanks will be allowed on roof tops other than for temporary roof repairs and shall be limited to not more than thirty pounds of propane. The tank shall be removed from the roof at the completion of the work day. No storage cages will be allowed to be stored under any eave on the building with an overhang greater than two feet or if the overhang has any type of opening into the main building (either exterior or interior).
(Ord. 45-05. Passed 7-11-05.)