1484.18 CAPACITY.
   Capacities of different sizes and lengths of pipe in cubic feet per hour with a pressure drop of 0.3 inch of water column of gas of 0.60 sp. gr. are shown in Table 1. In using this table, no allowance for an ordinary number of fittings is necessary.
TABLE 1
CAPACITY OF PIPE OF DIFFERENT DIAMETERS AND LENGTHS
IN CUBIC FEET PER HOUR WITH PRESSURE DROP OF 0.3 INCH AND SPECIFIC GRAVITY OF 0.60
IRON PIPE SIZE (IPS) INCHES
Length of Pipe (Ft.)
1/2
3/4
1
1-1/4
1-1/2
2
3
4
6
8
15
76
172
345
750
1,220
2,480
6,500
13,800
38,700
79,000
30
52
120
241
535
850
1,780
4,700
9,700
27,370
55,850
45
43
99
199
435
700
1,475
3,900
7,900
23,350
45,000
60
38
86
173
380
610
1,290
3,450
6,800
19,330
39,500
75
77
155
345
545
1,120
3,000
6,000
17,310
35,300
90
70
141
310
490
1,000
2,700
5,500
15,800
32,250
105
65
131
285
450
920
2,450
5,100
14,620
29,850
120
120
270
420
860
2,300
4,800
13,680
27,920
150
109
242
380
780
2,090
4,350
12,240
25,000
180
100
225
350
720
1,950
4,000
11,160
22,800
210
92
205
320
660
1,780
3,700
10,330
21,100
240
190
300
620
1,680
3,490
9,600
19,740
270
178
285
580
1,580
3,250
9,000
18,610
300
170
270
545
1,490
3,000
8,500
17,660
450
140
226
450
1,230
2,500
7,000
14,420
600
119
192
390
1,030
2,130
6,000
12,480
 
(Ord. 368. Passed 8-4-50.)