§ 4-2-36 SAME; SERVICE DISCONNECTING MEANS.
   Section 230-70(A)(1) of the Electrical Code shall be deemed to be here by amended to include the following additional sentences: “The service disconnecting means located inside a building shall be located immediately adjacent to and within sight of a walk-in exit door and not within the swinging area of such door. The distance between the disconnecting means and such exit door shall not exceed twelve (12) feet open travel measured from the exit door to the disconnecting means”.