1305D.1 Compliance Deadline. No later than December 31, 2011 ("Compliance Deadline"), the owner of each building subject to this Chapter shall self-certify that the entire building meets the standards specified in this Chapter 13D, and if the building is not certified, the building owner shall make such repairs as may be required to conform to this Chapter.
1305D.2 Stay of compliance deadline. The Compliance Deadline stated in Section 1305D.1 shall be stayed for up to two years from the date of an application for a demolition permit for any building subject to this Chapter. If the building is demolished and a Certificate of Completion issued by the Department before the end of the two-year postponement, the requirements of this Chapter shall not apply. If the building is not demolished after the expiration of two year, the provisions of this Chapter 13D shall apply even though the demolition permit is still in effect or a new demolition permit has been issued.
(Amended by Ord. 65-19, File No. 190136, App. 4/12/2019, Eff. 5/13/2019)
1306D.1 Mercury Content. The mercury content of each 4-foot linear fluorescent lamp installed after the Compliance Deadline in a luminaires in a building subject to this Chapter shall not exceed 5 mg. The mercury content of each 8-foot linear fluorescent lamp installed after the Compliance Deadline in a luminaires in a building subject to this Chapter shall not exceed 10 mg.
1306D.2. Energy efficiency. The lamp and ballast system in each luminaire that utilizes one or more 4-foot or 8-foot linear fluorescent lamp to provide illumination in a building subject to this Chapter 13D must meet at least one of the following requirements:
1. The lamp and ballast system emits 81 or more lumens per watt of electricity consumed.
2. The luminaire is controlled by an occupancy sensor control device that does not control an area in the building of more than 250 square feet.
3. The luminaire is fitted with a lighting efficiency measure approved by the Director as equivalent to the measures in subsection (1) or (2).
4. The Director finds, based on the facts of the particular building and luminaire, that the energy savings from installing lighting efficiency measures meeting the requirements of this Section will be so insignificant over the life of the luminaire that the measure is not cost efficient.
5. If the owner of a Commercial Building elects to meet the requirements of this Section 1306D.2 with measures that require permits, such permits shall comply with all other applicable requirements of this Code and all other applicable state and local laws.
(Amended by Ord. 65-19, File No. 190136, App. 4/12/2019, Eff. 5/13/2019)
The director, after consulting with the Department of the Environment, and in accordance with Section 104A.2.1 of this Code, shall adopt, and may amend, reasonable rules, guidelines and forms for implementing the provisions and intent of this Chapter.
In undertaking the enforcement of this Chapter, the City and County of San Francisco is assuming an undertaking only to promote the general welfare. It is not assuming, nor is it imposing on its officers and employees, an obligation for breach of which it is liable in money damages to any person who claims that such breach proximately caused injury.
If any provision or clause of this Chapter or the application thereof to any person or circumstance is held to be unconstitutional or to be otherwise invalid by any court of competent jurisdiction, such invalidity shall not affect other provisions, and clauses of this Chapter are declared to be severable.