SECTION 1505 – FIRE CLASSIFICATION
1505.1  Revise the second sentence as follows:
1505.1  General.  Roof assemblies shall be divided into the classes defined below. Class A or B roof assemblies and roof coverings required to be listed by this section shall be tested in accordance with ASTM E 108 or UL 790.
(Amended by Ord. 65-19, File No. 190136, App. 4/12/2019, Eff. 5/13/2019)
1505.1  Add the following at the end of the first paragraph:
Class B or better roof coverings shall be used on all buildings.
1505.1  Add the following second exception:
   2.   Detached accessory structures with a roof of less than 200 square feet (18.58 m2 ) may have roof cover- ings of Class A, B or C.
Table 1505.1  Revise the table as follows:
TABLE 1505.1 – MINIMUM ROOF COVERING CLASSIFICATION FOR TYPES OF CONSTRUCTION
 
IA
IB
IIA
IIB
IIIA
IIIB
IV
VA
VB
B
B
B
B
B
B
B
B
B