Skip to code content (skip section selection)
Compare to:
San Francisco Overview
San Francisco Building Inspection Commission (BIC) Codes
SAN FRANCISCO BUILDING INSPECTION COMMISSION CODES
BUILDING CODE 2016 Edition
PUBLISHER'S NOTE
PREFACE
Chapter 1 SCOPE AND ADMINISTRATION
Chapter 1A SAN FRANCISCO ADMINISTRATION
Chapter 2 DEFINITIONS
Chapter 3 USE AND OCCUPANCY CLASSIFICATION
Chapter 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
Chapter 5 GENERAL BUILDING HEIGHTS AND AREAS
Chapter 6 TYPES OF CONSTRUCTION
Chapter 7 FIRE AND SMOKE PROTECTION FEATURES
Chapter 7A [SFM] MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE
Chapter 8 INTERIOR FINISHES
Chapter 9 FIRE PROTECTION SYSTEMS
Chapter 10 MEANS OF EGRESS
Chapter 10A SECURITY REQUIREMENTS
Chapter 11 RESERVED
Chapter 11A HOUSING ACCESSIBILITY
Chapter 11B ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMMODATIONS, COMMERCIAL BUILDINGS AND PUBLICLY FUNDED HOUSING
Chapter 11C RESERVED
Chapter 11D MANDATORY ACCESSIBILITY IMPROVEMENTS FOR BUILDINGS WITH A PLACE OF PUBLIC ACCOMMODATION
Chapter 12 INTERIOR ENVIRONMENT
Chapter 13 ENERGY EFFICIENCY
Chapter 13A COMMERCIAL WATER CONSERVATION
Chapter 13B CONSTRUCTION AND DEMOLITION DEBRIS RECOVERY PROGRAM
Chapter 13C [RESERVED]
Chapter 13D COMMERCIAL LIGHTING EFFICIENCY
Chapter 14 EXTERIOR WALLS
Chapter 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
Chapter 16 STRUCTURAL DESIGN
Chapter 16A STRUCTURAL DESIGN
Chapter 17 SPECIAL INSPECTIONS AND TESTS
Chapter 17A SPECIAL INSPECTIONS AND TESTS
Chapter 18 SOILS AND FOUNDATIONS
Chapter 18A SOILS AND FOUNDATIONS
Chapter 19 CONCRETE
Chapter 19A CONCRETE
Chapter 20 ALUMINUM
Chapter 21 MASONRY
Chapter 21A MASONRY
Chapter 22 STEEL
Chapter 22A STEEL
Chapter 23 WOOD
Chapter 24 GLASS AND GLAZING
Chapter 25 GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
Chapter 26 PLASTIC
Chapter 27 ELECTRICAL
Chapter 28 MECHANICAL SYSTEMS
Chapter 29 PLUMBING SYSTEMS
Chapter 30 ELEVATORS AND CONVEYING SYSTEMS
Chapter 31 SPECIAL CONSTRUCTION
Chapter 31A SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING MAINTENANCE
Chapter 31B [DPH] PUBLIC SWIMMING POOLS
Chapter 31C [DPH] RADIATION
Chapter 31D [DPH] FOOD ESTABLISHMENTS
Chapter 31E RESERVED
Chapter 31F [SLC] MARINE OIL TERMINALS
Chapter 32 ENCROACHMENTS INTO PUBLIC RIGHT-OF-WAY
Chapter 33 SAFEGUARDS DURING CONSTRUCTION
Chapter 34 RESERVED
Chapter 34A EXISTING STRUCTURES
Chapter 35 REFERENCED STANDARDS
Chapter 36 CALIFORNIA RESIDENTIAL CODE (CRC)
CALIFORNIA BUILDING CODE (CBC) APPENDICES
ADMINISTRATIVE BULLETINS
ELECTRICAL CODE 2016 Edition
EXISTING BUILDING CODE 2016 Edition
GREEN BUILDING CODE 2016 Edition
HOUSING CODE 2016 Edition
MECHANICAL CODE 2016 Edition
PLUMBING CODE 2016 Edition
Table of Amendments

You are viewing an archived code

Chapter 10A
SECURITY REQUIREMENTS
SECTION 1001A – SCOPE
1001A.1  General.  This chapter shall apply to all Group R, Division 1 and R, Division 2 Occupancies.
1001A.2  Apartment houses.  Apartment houses (Group R, Division 1 and R, Division 2 Occupancies) and buildings containing more than two residential condominium units shall meet the security requirements of this chapter.
1001A.3  Hotels and motels.  Hotels and motels shall comply with the security requirements of this chapter. For the purpose of this chapter, any building open to the public and offering accommodations to transient persons for compensation shall be considered as a hotel or motel.
SECTION 1002A – DEFINITIONS
   For the purpose of this chapter, certain terms are defined as follows:
   AUXILIARY LOCKING DEVICE is a secondary locking system added to the primary locking system to provide additional security.
   BURGLARY-RESISTANT GLAZING MATERIALS are materials which are defined in ANSI/UL Standard 972.
   DEADBOLT is a lock bolt which must be actuated by a key, a knob or thumb-turn and when projected becomes locked against return by end pressure, and does not have spring action, as a latch bolt does. A SINGLE CYLINDER DEADBOLT is a deadbolt lock which is activated from the outside by a key and from the inside by a knob, thumb-turn lever or similar mechanism. A DOUBLE CYLINDER DEADBOLT is a deadbolt which can only be activated by a key from both interior and exterior.
   DEADLATCH or DEADLOCKING LATCH BOLT is a spring-actuated latch bolt having a beveled end and an incorporated plunger which, when depressed, automatically locks the projected latch bolt against return by end pressure.
   PRIMARY LOCKING DEVICE is the single locking system on a door or window unit whose function is to prevent unauthorized intrusion.
   WINDOW LOCKING DEVICE is part of a window assembly which is intended to prevent movement of the movable sash, and may be the sash lock or sash operator.
SECTION 1003A – GENERAL REQUIREMENTS FOR SECURITY
1003A.1  Clearances.  The clearance between the door and the frame and between meeting edges of doors swinging in pairs shall not exceed 1/8 inch (3.2 mm). The clearance between the door and the floor with either flush or raised sill shall be not more than 3/4 inch (19.1 mm).
1003A.2  Door assemblies.  Excluding main entry doors, all exterior swinging doors, and swinging interior and exterior entry doors, including assemblies and related hardware, which are directly accessible from the ground level or by stairs or by ramp, or from roof areas, or parking lot, or garage areas, shall meet the requirements of Grade 20 of ANSI/ASTM F476, Standard Test Methods for Security of Swinging Door Assemblies.
   All such doors shall be self-closing continuously locked, and openable from the interior with no special effort or knowledge or key. Where electrically operated locks are used, they must be self-latching and locking and shall have manual release capability from the interior requiring no special effort or knowledge or key.
1003A.2.1  Main entrance.  All main entry doors, including electrically operated main entry doors, shall be provided with a primary locking device. “Main entry doors” shall be defined as exterior doors leading directly into the lobby, registration areas or employee entrances.
1003A.2.2  Viewer.  Each door shall be provided with a minimum 135-degree viewer which does not have sighting capability when viewed from the outside. Mounting height shall not exceed 58 inches (1473 mm).
1003A.3  Fire-rated door assemblies.  Fire-rated door assemblies shall meet the requirements of Grade 20, ANSI/ASTM F476.
1003A.4  Glazing.  All glazing within 40 inches (1016 mm) of any locking mechanism of exterior and interior dwelling unit doors shall be of safety glass or burglar-resistant glazing. This requirement shall not exempt the swinging door assembly standards of Grade 20 of ANSI/ ASTM F476.
1003A.5  Metal gates.  Metal gates shall conform to the following:
   1.   Latch bolt protected by a security plate.
   2.   Hinges, bolts, screws shall be nonremovable.
   3.   Areas within 40 inches (1016 mm) of latch mechanism protected by mesh screen or approved equal.
   4.   Interior release mechanism protected with cover.
   5.   For electrically operated locks, see Section 1003A.2.
1003A.6  Sliding glass doors.  Sliding glass door assemblies shall be so designed that the door cannot be lifted from the track when the door is in a locked position.
   In addition to the primary locking device, all sliding glass doors shall have an auxiliary locking device permanently mounted and not accessible from the exterior of the building but easily accessible from the interior.
1003A.7  Sliding glass windows.  Sliding glass window assemblies shall be so designed that the moving panel cannot be lifted from the track while in a closed position.
1003A.8  Parking areas.  Parking space numbering shall not correspond to the guest room or dwelling unit number.
   Exterior parking areas and access thereto shall be provided with a minimum of 1/2 foot-candle (5.38 lx) of light on the parking surface when the area is unoccupied. Lighting devices shall be protected by weather- and vandalism-resistant covers.
SECTION 1004A – SPECIAL HOTEL AND MOTEL SECURITY REQUIREMENTS
1004A.1  Entry doors to guest rooms.
   EXCEPTION:  Residential care facilities licensed by the State of California under Title 22 of the California Code of Regulations shall not be required to comply with the requirements of this subsection.
   Locks shall be a combination of minimum 1/2-inch (12.7 mm) throw deadlatch with a minimum 1-inch (25.4 mm) deadbolt.
   All locks shall be capable of locking out all keys, except the emergency keys for guest privacy while inside the room, and so constructed that both deadlatch and deadbolt are retracted simultaneously by a single knob or lever.
1004A.2  Communicating door between guest rooms.  Communicating doors between guest rooms if not required to be fire-rated shall meet the requirements of Grade 20 of ANSI/ASTM F476 and be of minimum 1 3/8-inch (35 mm) bonded wood core or approved equal.
1004A.3  Roof openings.  All skylights leading directly to guest rooms, offices and enclosed commercial space shall be provided with burglary-resistant glazing as defined in Section 1002A.
1004A.4  Message and key box – front desk.  The message and room key location at the front desk shall not be visible from public view so as to determine an unoccupied room.
SECTION 1005A – SPECIAL APARTMENT HOUSE AND CONDOMINIUM SECURITY REQUIREMENTS
1005A.1  Voice communications.  A two-way voice communication system shall be provided between the common entry door and all interior dwelling units. All systems shall provide direct communication.
1005A.2  Lighting.  Lighting shall be a minimum of 1/2 foot-candle (5.38 lx) of light on the ground surface from the street to the entry door. Lighting devices shall be protected by weather- and vandalism-resistant covers.
1005A.3  Master keying.  Exterior and main entrance door locks shall not be on any master key system.
1005A.4  Entry doors.  Entry doors and door assemblies shall comply with the following:
1005A.4.1  Locks shall be combination 1/2-inch (12.7 mm) throw deadlatch with a minimum 1-inch (25.4 mm) throw deadbolt, and so constructed that both the deadlatch and deadbolt retract simultaneously by knob or lever. The deadbolt shall have the ability to be thrown from the exterior.
1005A.5  Exit doors.  All exit doors from corridors to exit stairways and from interior stairwells and interior fire escapes shall meet the requirements of Grade 20 of ANSI/ ASTM F476 and be continuously locked from the outside.
   Locking devices shall be self-latching or self-locking and shall be openable from the interior with no special effort or knowledge or key. [See Section 1008.1.9.]
1005A.6  Glazed openings.  Glazed openings accessible from the ground level, by stairs, ramps, parking lots or garage areas, shall be with approved safety glass or burglar-resistant glazing as defined in Section 1002A. Protective iron grill work may only be installed where it does not interfere with the required means of egress.
1005A.7  Roof openings.  All skylights leading directly to interior corridors, stairwells, dwelling units and utility rooms shall be provided with burglary-resistant glazing as defined in Section 1002A.
1005A.8  Garage doors.  All doors of the sectional overhead, one-piece overhead, swing or sliding types used on the exterior of a building shall conform to the following standards:
1005A.8.1  Panels of wood doors shall be at least 5/16-inch (7.94 mm) thick, except sectional overhead doors may have panels 1/4-inch (6.35 mm) thick.
1005A.8.2  Aluminum doors shall be constructed of at least 0.025-inch (0.635 mm) thick sheet aluminum, riveted, welded or bolted to framing members at least 12 inches (305 mm) on center.
1005A.8.3  Steel doors shall be constructed of at least 0.023-inch (0.584 mm) thick galvanized steel, riveted, welded or bolted to framing members at least 12 inches (305 mm) on center.
1005A.8.4  Fiberglass sectional doors shall be constructed of formed fiberglass panels of density of at least 5 1/2 oz. per square foot (1678 g/m2 ), pressure sealed to aluminum framing members.
1005A.8.5  Overhead doors shall be made lockable by either:
   For doors 16 feet (4877 mm) wide or less, a slide bolt – minimum diameter 3/8-inch (9.5 mm) minimum projection 1-1/2 inches (38 mm) – locking into the door jamb, capable of utilizing a padlock with a minimum 9/32-inch (7.14 mm) shackle. For doors over 16 feet (4877 mm) wide, except sectional doors, two slide bolt locks shall be required. Slide bolt assemblies shall be attached to the door with bolts which are nonremovable from the exterior.
   Electrical operator with automatic locking capability, either inherently in the mechanism or as an added feature.
   By at least one single-bar lock mounted in the end stile, with locking bar or bolt extending into the receiving guide a minimum of 1 inch (25.4 mm), and with minimum five-pin tumble operation. For doors over 16 feet (4877 mm) wide, except sectional doors, two single-bar locks shall be required.
   Center locking-handle devices will require actuating straps to be enclosed by rigid conduits securely fastened to the door.
1005A.8.6  Swinging garage doors shall be lockable by a cylinder deadbolt.
1005A.8.7  Doors operated by electrical means shall be provided with manual release capability from the interior, requiring no special effort or knowledge or key.
1005A.8.8  Manually operated chain-driven garage doors shall require approval of the Authority Having Jurisdiction.