Skip to code content (skip section selection)
Compare to:
San Francisco Overview
San Francisco Building Inspection Commission (BIC) Codes
SAN FRANCISCO BUILDING INSPECTION COMMISSION CODES
BUILDING CODE 2016 Edition
PUBLISHER'S NOTE
PREFACE
Chapter 1 SCOPE AND ADMINISTRATION
Chapter 1A SAN FRANCISCO ADMINISTRATION
Chapter 2 DEFINITIONS
Chapter 3 USE AND OCCUPANCY CLASSIFICATION
Chapter 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
Chapter 5 GENERAL BUILDING HEIGHTS AND AREAS
Chapter 6 TYPES OF CONSTRUCTION
Chapter 7 FIRE AND SMOKE PROTECTION FEATURES
Chapter 7A [SFM] MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE
Chapter 8 INTERIOR FINISHES
Chapter 9 FIRE PROTECTION SYSTEMS
Chapter 10 MEANS OF EGRESS
Chapter 10A SECURITY REQUIREMENTS
Chapter 11 RESERVED
Chapter 11A HOUSING ACCESSIBILITY
Chapter 11B ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMMODATIONS, COMMERCIAL BUILDINGS AND PUBLICLY FUNDED HOUSING
Chapter 11C RESERVED
Chapter 11D MANDATORY ACCESSIBILITY IMPROVEMENTS FOR BUILDINGS WITH A PLACE OF PUBLIC ACCOMMODATION
Chapter 12 INTERIOR ENVIRONMENT
Chapter 13 ENERGY EFFICIENCY
Chapter 13A COMMERCIAL WATER CONSERVATION
Chapter 13B CONSTRUCTION AND DEMOLITION DEBRIS RECOVERY PROGRAM
Chapter 13C [RESERVED]
Chapter 13D COMMERCIAL LIGHTING EFFICIENCY
Chapter 14 EXTERIOR WALLS
Chapter 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
Chapter 16 STRUCTURAL DESIGN
Chapter 16A STRUCTURAL DESIGN
Chapter 17 SPECIAL INSPECTIONS AND TESTS
Chapter 17A SPECIAL INSPECTIONS AND TESTS
Chapter 18 SOILS AND FOUNDATIONS
Chapter 18A SOILS AND FOUNDATIONS
Chapter 19 CONCRETE
Chapter 19A CONCRETE
Chapter 20 ALUMINUM
Chapter 21 MASONRY
Chapter 21A MASONRY
Chapter 22 STEEL
Chapter 22A STEEL
Chapter 23 WOOD
Chapter 24 GLASS AND GLAZING
Chapter 25 GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
Chapter 26 PLASTIC
Chapter 27 ELECTRICAL
Chapter 28 MECHANICAL SYSTEMS
Chapter 29 PLUMBING SYSTEMS
Chapter 30 ELEVATORS AND CONVEYING SYSTEMS
Chapter 31 SPECIAL CONSTRUCTION
Chapter 31A SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING MAINTENANCE
Chapter 31B [DPH] PUBLIC SWIMMING POOLS
Chapter 31C [DPH] RADIATION
Chapter 31D [DPH] FOOD ESTABLISHMENTS
Chapter 31E RESERVED
Chapter 31F [SLC] MARINE OIL TERMINALS
Chapter 32 ENCROACHMENTS INTO PUBLIC RIGHT-OF-WAY
Chapter 33 SAFEGUARDS DURING CONSTRUCTION
Chapter 34 RESERVED
Chapter 34A EXISTING STRUCTURES
Chapter 35 REFERENCED STANDARDS
Chapter 36 CALIFORNIA RESIDENTIAL CODE (CRC)
CALIFORNIA BUILDING CODE (CBC) APPENDICES
ADMINISTRATIVE BULLETINS
ELECTRICAL CODE 2016 Edition
EXISTING BUILDING CODE 2016 Edition
GREEN BUILDING CODE 2016 Edition
HOUSING CODE 2016 Edition
MECHANICAL CODE 2016 Edition
PLUMBING CODE 2016 Edition
Table of Amendments

You are viewing an archived code

Chapter 9
FIRE PROTECTION SYSTEMS
SECTION 901 – GENERAL
901.4  Add a second paragraph as follows:
   Notwithstanding any other provisions of the California Building Code or other codes or regulations, Fire Department connections shall have 3-inch (76.2 mm) National Standard hose threads.
SECTION 903 – AUTOMATIC SPRINKLER SYSTEMS
903.2.8  Add exception 5 as follows:
   5.   An automatic residential fire sprinkler system shall not be required when additions or alterations are made to existing townhouses, one- and two- family dwellings not more than three stories above grade plane that do not have an automatic residential fire sprinkler system installed. [CRC 1.1.3, R313.1, R313.2]
Table 903.2.11.6  Add a new line to the end of the Table as follows:
TABLE 903.2.11.6
ADDITIONAL REQUIRED SUPPRESSION SYSTEMS
 
SECTION
SUBJECT
3202.3.4
Pedestrian Walkways over Public Streets
 
SECTION 905 – STANDPIPE SYSTEMS
905.3.4  Revise this section as follows:
905.3.4  Stages.  Stages greater than 1,000 square feet in area (93 m2) shall be equipped with a Class III wet standpipe system with 1-1/2-inch and 3-inch (38 mm and 76.2 mm) hose connections on each side of the stage.
SECTION 907 – FIRE ALARM AND DETECTION SYSTEMS
907.2.9.1  Revise Item 3 and Item 4 as follows:
   3.   The building contains more than 6 dwelling units or sleeping units.
   4.   Congregate living facilities or congregate residences three or more stories in height or having an occupant load of 11 or more.
907.2.9.5  Add the following section:
907.2.9.5  Automatic smoke detection system.  An auto- matic smoke detection system that activates the occupant notification system in accordance with Section 907.6 shall be installed throughout all interior corridors serving sleeping units.
Exceptions:
   1.   An automatic smoke detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exit or to an exterior exit access that leads directly to an exit.
   2.   An automatic smoke detection system is not required in buildings when all of the following conditions are met:
      2.1.   The building is equipped throughout with a supervised automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
      2.2.   The notification devices will activate upon sprinkler water flow; and
      2.3.   At least one manual pull station is installed in an approved location.
907.2.11.6  Add a second paragraph as follows:
   Group R-3 congregate living facilities having an occupant load of 6 or more shall be provided with a manual fire alarm system.
SECTION 912 – FIRE DEPARTMENT CONNECTIONS
912  Add the following section:
912.7  Number of connections required.  Sprinkler systems requiring a 4-inch (101.6 mm) or larger water service shall have two or more inlet connections as necessary to meet hydraulic demand.
(Amended by Ord. 65-19, File No. 190136, App. 4/12/2019, Eff. 5/13/2019)