§ 7-4-17 SPECIFICATIONS FOR LAYING OF SEWER PIPE.
   (A)   The contractor must install pipe according to state and local codes.
   (B)   Angle of grade of pipe must be 2% or more.
   (C)   There shall be no angles in pipe greater than 45 degrees.
   (D)   The pipe must be at least four inches in diameter in size.
   (E)   Property owners: minimum quality pipe to be used in system: schedule 40 PVC.
   (F)   For going through cesspools, which have been drained and refilled, the minimum quality pipe to be used shall be schedule 40 PVC.
   (G)   (1)   Each horizontal drainage pipe shall be provided with a cleanout at its upper terminal and at the end of each run of piping, which is more than 100 feet (30.4 m) or fraction there of in length.
      (2)   Each cleanout shall be installed so that it opens in a direction opposite to the flow of the soil or waste.
      (3)   Each cleanout extension shall be considered as drainage piping and each 90-degree cleanout extension shall be extended from a “Y” type fitting or other approved fitting of equivalent sweep.
      (4)   Each cleanout for an interceptor shall be outside of such interceptor.
(1992 Code, § 7-1-1217) (Ord. 07-01, passed 1-22-2007)