(A) Where a booster pump has been installed on the service line to or within any premises, such pump shall be equipped with a low pressure cut-off device designed to shut off the booster pump when the pressure in the service line on the suction side of the pump drops to ten pounds per square inch gage or less.
(B) The water consumer shall maintain the low pressure cut-off device in proper working order and shall certify to the Safety-Service Director, at least once each year, that the device is operable.
(`82 Code, § 1041.11) (Ord. 88-58, passed 7-5-88)