§ 92.097 FIRE EXTINGUISHING EQUIPMENT.
   (A)   All fire extinguishers must be of an approved type.
   (B)   Fire extinguishers of all types must be kept filled with the proper extinguishing agent at all times.
   (C)   All fire extinguishers of the soda-acid or foam type must be properly recharged at least once a year and the date of recharge shown on a tag attached to each extinguisher.
   (D)   All CO2 (carbon dioxide) fire extinguishers shall be kept sealed at all times. At any time the seal is broken, the extinguisher shall be given a weight test to determine if the proper amount of CO2 is present, recharged if necessary, and resealed.
   (E)   All fire extinguishing equipment shall be located in an easily accessible and conspicuous place approved by the Fire Chief or an officer of the Fire Department.
   (F)   The owners or person in charge of any building that is now equipped or may hereafter be equipped with dry or wet line standpipes with inlet or outlet connections shall cause these connections and fittings to be kept well oiled, loose, and ready for immediate use in case of fire. All hoses shall be properly cared for at all times.
   (G)   Prior to the installation of any fire extinguishers or fire extinguishing equipment, the Fire Chief shall be consulted as to the proper type, size, and location of the installation.
   (H)   No extinguisher of the vaporizing liquid type, carbon tetrachloride, shall be installed in any location where any number of people are allowed to congregate, such as lobbies or auditoriums.
   (I)   It shall be unlawful to remove from its proper place any fire apparatus or appliance except for inspection or in case of emergency.
(1969 Code, § 9-105) Penalty, see § 92.999