1381.02 ADDITIONS, INSERTIONS AND CHANGES.
   The International Property Maintenance Code, 2012 Edition is amended and revised in the following respects:
Major Differences between the 2003 and 2012 IPMC Editions
•   Expanded on Section 102.7 Referenced codes and standards
   o   [A] 102.7 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 8 and considered part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections 102.7.1 and 102.7.2.
Exception: Where enforcement of a code provision would violate the conditions of the listing of the equipment or appliance, the conditions of the listing shall apply.
[A] 102.7.1 Conflicts. Where conflicts occur between provisions of this code and the referenced standards, the provisions of this code shall apply.
[A] 102.7.2 Provisions in referenced codes and standards.
Where the extent of the reference to a referenced code or standard includes subject matter that is within the scope of this code, the provisions of this code, as applicable, shall take precedence over the provisions in the referenced code or standard.
•   Added Section 102.9 Application of references.
   o   102.9 Application of references. References to chapter or section numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code.
•   Combined Sections 104.1 General & 104.2 Rule Making Authority
•   Removed Section 104.8 Coordination of Inspections.
•   Added Section 105.5 Approved materials and equipment.
   o   105.5 Approved materials and equipment. Materials, equipment and devices approved by the code official shall be constructed and installed in accordance with such approval.
•   Added Section 105.6 Research reports.
   o   105.6 Research reports. Supporting data, where necessary to assist in the approval of materials or assemblies not specifically provided for in this code, shall consist of valid research reports from approved sources.
•   Added Section 107.4 Unauthorized tampering.
   o   107.4 Unauthorized tampering. Signs, tags or seals posted or affixed by the code official shall not be mutilated, destroyed or tampered with, or removed without authorization from the code official.
•   Added Section 108.1.5 Dangerous structure or premises.
   o   108.1.5 Dangerous structure or premises. For the purpose of this code, any structure or premises that has any or all of the conditions or defects described below shall be considered dangerous:
      1.    Any door, aisle, passageway, stairway, exit or other means of egress that does not conform to the approved building or fire code of the jurisdiction as related to the requirements for existing buildings.
      2.    The walking surface of any aisle, passageway, stairway, exit or other means of egress is so warped, worn loose, torn or otherwise unsafe as to not provide safe and adequate means of egress.
      3.    Any portion of a building, structure or appurtenance that has been damaged by fire, earthquake, wind, flood, deterioration, neglect, abandonment, vandalism or by any other cause to such an extent that it is likely to partially or completely collapse, or to become detached or dislodged.
      4.    Any portion of a building, or any member, appurtenance or ornamentation on the exterior thereof that is not of sufficient strength or stability, or is not so anchored, attached or fastened in place so as to be capable of resisting natural or artificial loads of one and one-half the original designed value.
      5.    The building or structure, or part of the building or structure, because of dilapidation, deterioration, decay, faulty construction, the removal or movement of some portion of the ground necessary for the support, or for any other reason, is likely to partially or completely collapse, or some portion of the foundation or underpinning of the building or structure is likely to fail or give way.
      6.    The building or structure, or any portion thereof, is clearly unsafe for its use and occupancy.
      7.    The building or structure is neglected, damaged, dilapidated, unsecured or abandoned so as to become an attractive nuisance to children who might play in the building or structure to their danger, becomes a harbor for vagrants, criminals or immoral persons, or enables persons to resort to the building or structure for committing a nuisance or an unlawful act.
      8.    Any building or structure has been constructed, exists or is maintained in violation of any specific requirement or prohibition applicable to such building or structure provided by the approved building or fire code of the jurisdiction, or of any law or ordinance to such an extent as to present either a substantial risk of fire, building collapse or any other threat to life and safety.
      9.    A building or structure, used or intended to be used for dwelling purposes, because of inadequate maintenance, dilapidation, decay, damage, faulty construction or arrangement, inadequate light, ventilation, mechanical or plumbing system, or otherwise, is determined by the code official to be unsanitary, unfit for human habitation or in such a condition that is likely to cause sickness or disease.
      10.    Any building or structure, because of a lack of sufficient or proper fire-resistance-rated construction, fire protection systems, electrical system, fuel connections, mechanical system, plumbing system or other cause, is determined by the code official to be a threat to life or health.
      11.    Any portion of a building remains on a site after the demolition or destruction of the building or structure or whenever any building or structure is abandoned so as to constitute such building or portion thereof as an attractive nuisance or hazard to the public.
•   Added Section 108.2.1 Authority to disconnect service utilities.
   o   108.2.1 Authority to disconnect service utilities. The code official shall have the authority to authorize disconnection of utility service to the building, structure or system regulated by this code and the referenced codes and standards set forth in Section 102.7 in case of emergency where necessary to eliminate an immediate hazard to life or property or when such utility connection has been made without approval. The code official shall notify the serving utility and, whenever possible, the owner and occupant of the building, structure or service system of the decision to disconnect prior to taking such action. If not notified prior to disconnection the owner or occupant of the building structure or service system shall be notified in writing as soon as practical thereafter.
•   Added Section 108.6 Abatement methods.
   o   108.6 Abatement methods. The owner, operator or occupant of a building, premises or equipment deemed unsafe by the code official shall abate or cause to be abated or corrected such unsafe conditions either by repair, rehabilitation, demolition or other approved corrective action.
•   Added Section 108.7 Record.
   o   108.7 Record. The code official shall cause a report to be filed on an unsafe condition. The report shall state the occupancy of the structure and the nature of the unsafe condition.
•   Added Section 112 - Stop Work Order
   o   112.1 Authority. Whenever the code official finds any work regulated by this code being performed in a manner contrary to the provisions of this code or in a dangerous or unsafe manner, the code official is authorized to issue a stop work order.
   •   [A] 112.2 Issuance. A stop work order shall be in writing and shall be given to the owner of the property, to the owner's agent, or to the person doing the work. Upon issuance of a stop work order, the cited work shall immediately cease. The stop work order shall state the reason for the order and the conditions under which the cited work is authorized to resume.
   •   112.3 Emergencies. Where an emergency exists, the code official shall not be required to give a written notice prior to stopping the work.
   •   [A] 112.4 Failure to comply. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be liable to a fine of not less than [AMOUNT] dollars or more than [AMOUNT] dollars.
•   Added Section 304.1.1 Unsafe conditions
   •   304.1.1 Unsafe conditions. The following conditions shall be determined as unsafe and shall be repaired or replaced to comply with the International Building Code or the International Existing Building Code as required for existing buildings:
         1.    The nominal strength of any structural member is exceeded by nominal loads, the load effects or the required strength;
         2.    The anchorage of the floor or roof to walls or columns, and of walls and columns to foundations is not capable of resisting all nominal loads or load effects;
         Structures or components thereof that have reached their limit state;
         4.   Siding and masonry joints including joints between the building envelope and the perimeter of windows, doors and skylights are not maintained, weather resistant or water tight;
         5.    Structural members that have evidence of deterioration or that are not capable of safely supporting all nominal loads and load effects;
         6.    Foundation systems that are not firmly supported by footings, are not plumb and free from open cracks and breaks, are not properly anchored or are not capable of supporting all nominal loads and resisting all load effects;
         7.    Exterior walls that are not anchored to supporting and supported elements or are not plumb and free of holes, cracks or breaks and loose or rotting materials, are not properly anchored or are not capable of supporting all nominal loads and resisting all load effects;
         8.    Roofing or roofing components that have defects that admit rain, roof surfaces with inadequate drainage, or any portion of the roof framing that is not in good repair with signs of deterioration, fatigue or without proper anchorage and incapable of supporting all nominal loads and resisting all load effects;
         9.    Flooring and flooring components with defects that affect serviceability or flooring components that show signs of deterioration or fatigue, are not properly anchored or are incapable of supporting all nominal loads and resisting all load effects;
         10.    Veneer, cornices, belt courses, corbels, trim, wall facings and similar decorative features not properly anchored or that are anchored with connections not capable of supporting all nominal loads and resisting all load effects;
         11.    Overhang extensions or projections including, but not limited to, trash chutes, canopies, marquees, signs, awnings, fire escapes, standpipes and exhaust ducts not properly anchored or that are anchored with connections not capable of supporting all nominal loads and resisting all load effects;
         12.    Exterior stairs, decks, porches, balconies and all similar appurtenances attached thereto, including guards and handrails, are not structurally sound, not properly anchored or that are anchored with connections not capable of supporting all nominal loads and resisting all load effects; or
         13.    Chimneys, cooling towers, smokestacks and similar appurtenances not structurally sound or not properly anchored, or that are anchored with connections not capable of supporting all nominal loads and resisting all load effects.
   •   Exceptions:
         When substantiated otherwise by an approved method.
         Demolition of unsafe conditions shall be permitted when approved by the code official.
•   Added Section 304.19 Gates.
   •   304.19 Gates. All exterior gates, gate assemblies, operator systems if provided, and hardware shall be maintained in good condition. Latches at all entrances shall tightly secure the gates.
•   Added Section 305.1.1 Unsafe conditions.
   •   305.1.1 Unsafe conditions. The following conditions shall be determined as unsafe and shall be repaired or replaced to comply with the International Building Code or the International Existing Building Code as required for existing buildings:
         1.    The nominal strength of any structural member is exceeded by nominal loads, the load effects or the required strength;
         2.    The anchorage of the floor or roof to walls or columns, and of walls and columns to foundations is not capable of resisting all nominal loads or load effects;
         3.    Structures or components thereof that have reached their limit state;
         4.    Structural members are incapable of supporting nominal loads and load effects;
         5.    Stairs, landings, balconies and all similar walking surfaces, including guards and handrails, are not structurally sound, not properly anchored or are anchored with connections not capable of supporting all nominal loads and resisting all load effects;
         6.    Foundation systems that are not firmly supported by footings are not plumb and free from open cracks and breaks, are not properly anchored or are not capable of supporting all nominal loads and resisting all load effects.
   •   Exceptions:
         1.    When substantiated otherwise by an approved method.
         2.    Demolition of unsafe conditions shall be permitted when approved by the code official.
•   Added Section 306 - Component Serviceability
•   306.1 General. The components of a structure and equipment therein shall be maintained in good repair, structurally sound and in a sanitary condition. Soils that have been subjected to any of the following conditions:
•   306.1.1 Unsafe conditions. Where any of the following conditions cause the component or system to be beyond its limit state, the component or system shall be determined as unsafe and shall be repaired or replaced to comply with the International Building Code as required for existing buildings:
1.1.    Collapse of footing or foundation system;
1.2.    Damage to footing, foundation, concrete or other structural element due to soil expansion;
1.3.    Adverse effects to the design strength of footing, foundation, concrete or other structural element due to a chemical reaction from the soil;
1.4.    Inadequate soil as determined by a geotechnical investigation;
1.5.    Where the allowable bearing capacity of the soil is in doubt; or
1.6.    Adverse effects to the footing, foundation, concrete or other structural element due to the ground water table.
      2.    Concrete that has been subjected to any of the following conditions:
         2.1.    Deterioration;
         2.2.    Ultimate deformation;
         2.3.    Fractures;
         2.4.    Fissures;
         2.5.    Spalling;
         2.6.    Exposed reinforcement; or
         2.7.    Detached, dislodged or failing connections.
      3.    Aluminum that has been subjected to any of the following conditions:
         3.1.    Deterioration;
         3.2.    Corrosion;
         3.3.    Elastic deformation;
         3.4.    Ultimate deformation;
         3.5.    Stress or strain cracks;
         3.6.    Joint fatigue; or
         3.7.    Detached, dislodged or failing connections.
      4.    Masonry that has been subjected to any of the following conditions:
         4.1.    Deterioration;
         4.2.    Ultimate deformation;
         4.3.    Fractures in masonry or mortar joints;
         4.4.    Fissures in masonry or mortar joints;
         4.5.    Spalling;
         4.6.    Exposed reinforcement; or
         4.7.    Detached, dislodged or failing connections.
      5.    Steel that has been subjected to any of the following conditions:
         5.1.    Deterioration;
         5.2.    Elastic deformation;
         5.3.    Ultimate deformation;
         5.4.    Metal fatigue; or
         5.5.    Detached, dislodged or failing connections.
      6.    Wood that has been subjected to any of the following conditions:
         6.1.    Ultimate deformation;
         6.2.    Deterioration;
         6.3.    Damage from insects, rodents and other vermin;
         6.4.    Fire damage beyond charring;
         6.5.    Significant splits and checks;
         6.6.    Horizontal shear cracks;
         6.7.    Vertical shear cracks;
         6.8.    Inadequate support;
         6.9.    Detached, dislodged or failing connections;
         6.10.    Excessive cutting and notching.
   Exceptions:
      1.    When substantiated otherwise by an approved method.
      2.    Demolition of unsafe conditions shall be permitted when approved by the code official.
•   Added Section 502.5 Public toilet facilities.
   o   502.5 Public toilet facilities. Public toilet facilities shall be maintained in a safe sanitary and working condition in accordance with the International Plumbing Code. Except for periodic maintenance or cleaning, public access and use shall be provided to the toilet facilities at all times during occupancy of the premises.
•   Added Section 506.3 Grease interceptors.
   o   506.3 Grease interceptors. Grease interceptors and automatic grease removal devices shall be maintained in accordance with this code and the manufacturer's installation instructions. Grease interceptors and automatic grease removal devices shall be regularly serviced and cleaned to prevent the discharge of oil, grease, and other substances harmful or hazardous to the building drainage system, the public sewer, the private sewage disposal system or the sewage treatment plant or processes. All records of maintenance, cleaning and repairs shall be available for inspection by the code official.
•   Added Section 604.3.1.1 Electrical Equipment.
   o   604.3.1.1 Electrical equipment. Electrical distribution equipment, motor circuits, power equipment, transformers, wire, cable, flexible cords, wiring devices, ground fault circuit interrupters, surge protectors, molded case circuit breakers, low-voltage fuses, luminaires, ballasts, motors and electronic control, signaling and communication equipment that have been exposed to water shall be replaced in accordance with the provisions of the International Building Code.
Exception: The following equipment shall be allowed to be repaired where an inspection report from the equipment manufacturer or approved manufacturer's representative indicates that the equipment has not sustained damage that requires replacement:
      1.   Enclosed switches, rated a maximum of 600 volts or less;
      2.    Busway, rated a maximum of 600 volts;
      3.    Panelboards, rated a maximum of 600 volts;
      4.    Switchboards, rated a maximum of 600 volts;
      5.    Fire pump controllers, rated a maximum of 600 voltss;
      6.    Manual and magnetic motor controllers;
      7.    Motor control centers;
      8.    Alternating current high-voltage circuit breakers;
      9.    Low-voltage power circuit breakers;
      10.    Protective relays, meters and current transformers;
      11.    Low- and medium-voltage switchgear;
      12.    Liquid-filled transformers;
      13.    Cast-resin transformers;
      14.    Wire or cable that is suitable for wet locations and whose ends have not been exposed to water;
      15.    Wire or cable, not containing fillers, that is suitable for wet locations and whose ends have not been exposed to water;
      16.    Luminaires that are listed as submersible;
      17.    Motors;
      18.    Electronic control, signaling and communication equipment.
•   Added Section 604.3.2 Abatement of electrical hazards associated with fire exposure.
   o   604.3.2 Abatement of electrical hazards associated with fire exposure. The provisions of this section shall govern the repair and replacement of electrical systems and equipment that have been exposed to fire.
•   Added Section 604.3.2.1 Electrical equipment.
   o   604.3.2.1 Electrical equipment. Electrical switches, receptacles and fixtures, including furnace, water heating, security system and power distribution circuits, that have been exposed to fire, shall be replaced in accordance with the provisions of the International Building Code.
Exception: Electrical switches, receptacles and fixtures that shall be allowed to be repaired where an inspection report from the equipment manufacturer or approved manufacturer's representative indicates that the equipment has not sustained damage that requires replacement.
•   Added Section 605.3 Luminaires.
   o   605.3 Luminaires. Every public hall, interior stairway, toilet room, kitchen, bathroom, laundry room, boiler room and furnace room shall contain at least one electric luminaire. Pool and spa luminaries over 15 V shall have ground fault circuit interrupter protection.
•   Added Section 605.4 Wiring.
   o   605.4 Wiring. Flexible cords shall not be used for permanent wiring, or for running through doors, windows, or cabinets, or concealed within walls, floors, or ceilings.
•   Added Section 704.1.1 Automatic sprinkler systems
   o   704.1.1 Automatic sprinkler systems. Inspection, testing and maintenance of automatic sprinkler systems shall be in accordance with NFPA 25.
      (Ord. 5-13. Passed 1-14-13.)