§ 1174.11 LIGHTING.
   For the purpose of providing consistent site lighting that does not produce glare and reduces the illumination of the night sky, the following lighting standards shall be followed.
   (a)   All non-decorative lighting shall use fully shielded, cut off type fixtures.
   (b)   Decorative, pedestrian scale lights are required in all areas of pedestrian activity including, but not limited to, sidewalks, streetscape areas and plazas.
   (c)   The maximum illumination at all property lines shall be 0.5 foot candles as demonstrated on a photometric plan.
   (d)   Light poles shall be consistent with the overall architectural theme of the site and be located in landscape islands located in vehicular use areas where possible.
   (e)   Neon accent lighting is prohibited on buildings.
   (f)   Light poles shall not exceed 30 feet in height.
(Ord. 2006-81, passed 8-28-2006)