§ 52.84 INSPECTION AND MAINTENANCE.
   (A)   It shall be the duty of the consumer at any premises on which backflow prevention devices required by these regulations are installed to have inspection, tests, maintenance and repair made per the following schedule or more often where inspections indicate a need or are specified in manufacturer's instructions.
      (1)   Fixed proper air gap separations shall be inspected to document that a proper vertical distance is maintained between the discharge point of the service line and the flood level rim of the receptacle at the time of installation and at least annually thereafter. Corrections to improper or by passed air gaps shall be made within 24 hours.
      (2)   Double check valve assemblies shall be inspected and tested at time of installation and at least annually thereafter, and required service performed within five days.
      (3)   Reduced pressure principle backflow prevention assemblies shall be tested at the time of installation and at least annually or more frequently if recommended by the manufacturer, and required service performed within five days.
   (B)   Testing shall be performed by a person who has been approved by the IEPA as competent to service the device. Proof of approval shall be in writing.
   (C)   Each device shall have a tag attached listing the date of most recent test or visual inspection, name of tester, and type and date of repairs.
   (D)   A maintenance log shall be maintained and include:
      (1)   Date of each test or visual inspection;
      (2)   Name and approval number of person performing the test or visual inspection;
      (3)   Test results;
      (4)   Repairs or servicing required;
      (5)   Repairs and date completed; and
      (6)   Servicing performed and date completed.
   (E)   Whenever backflow prevention devices required by these regulations are found to be defective, they shall be repaired or replaced at the expense of the consumer without delay as required by division (A) above.
   (F)   Backflow prevention devices shall not be bypassed, made inoperative, removed or otherwise made ineffective without specific authorization by the Superintendent of Water.
(Ord. 2840, passed 7-26-93)
§ 52.85 BOOSTER PUMPS.
   (A)   Where a booster pump has been installed on the service line to or within any premises, such pump shall be equipped with a low pressure cut-off device designed to shut-off the booster pump when the pressure in the service line on the suction side of the pump drops to 20 psi or less.
   (B)   It shall be the duty of the water consumer to maintain the low pressure cut-off device in proper working order and to certify to the Superintendent of Water, at least once a year, that the device is operable.
(Ord. 2840, passed 7-26-93)
§ 52.86 VIOLATIONS.
   (A)   The Superintendent of Water shall deny or discontinue, after reasonable notice to the occupants thereof, the water service to any premises wherein any backflow prevention device required by these regulations is not installed, tested, maintained and repaired in a manner acceptable to the Superintendent of Water, or if it is found that the backflow prevention device has been removed or bypassed, or if an unprotected cross-connection exists on the premises, or if a low pressure cut-off required by these regulations is not installed and maintained in working order.
   (B)   Water service to such premises shall not be restored until the consumer has corrected or eliminated such conditions or defects in conformance with these regulations and to the satisfaction of the Superintendent of Water, and the required reconnection fee is paid.
   (C)   Water service to such premises shall not be restored until the consumer has corrected or eliminated such conditions or defects in conformance with these regulations and to the satisfaction of the Superintendent of Utilities/Operations.
   (D)   Neither the (name of public water supply) the Superintendent of Water, or its agents or assigns shall be liable to any customers of the (name of public water supply) for any injury, damages or lost revenues which may result from termination of said customer's water supply per the terms of this subchapter, whether or not said termination of the water supply was with or without notice.
   (D)   The consumer responsible for back-siphoned material or contamination through backflow, if contamination of the potable water supply system occurs through an illegal cross-connection or an improperly installed, maintained or repaired device, or a device which has been bypassed, must bear the cost of clean-up of the potable water supply system.
   (E)   Any person found to be violating any provision of this subchapter shall be served with written notice stating the notice of the violation and providing a reasonable time limit for the satisfactory correction thereof. The offender shall, within the period of time stated in such notice, permanently cease all violation.
   (F)   Any person violating any of the provisions of this subchapter in addition to the fine provided, shall become liable to the city for any expense, loss or damage occasioned by the city by reason of such violation, whether the same was caused before or after notice.
(Ord. 2840, passed 7-26-93)