4-5-6: AMENDMENTS TO ELECTRICAL CODE:
The following amendments, deletions, additions and/or modifications are hereby made to the Inverness electrical code as adopted in section 4-5-5 of this chapter:
   A.   Section 250.104.(A)(1) of the Inverness electrical code is hereby amended by the addition of a subparagraph (a) thereto, which subparagraph shall provide as follows:
"(a) Grounding shall be bonded to the street side of the water supply with a bonding jumper around the water meter."
   B.   Article 300 of the Inverness electrical code is hereby amended by the addition of a new section 300-1A which shall read as follows:
"300-1A:   WIRING METHODS: Notwithstanding anything contained in this article or code to the contrary, all wiring for services, feeders and branch circuits installed on or within buildings shall be installed in electrical metallic tubing (as defined in article 348), in intermediate metal conduit (as defined in article 346), provided, however, (1) sections of armored cable (as defined in article 333) not exceeding six feet in length where necessary may be permitted but only with prior express and specific written approval of the electrical inspector; and (2) other approved methods which would provide equal or superior protection to conductors may be permitted but only if such method or methods have received the prior express and specific approval of the electrical inspector."
   C.   Section 310-13 of the Inverness electrical code is hereby amended by the addition of the following subparagraph at the end of the present text thereof, which subparagraph shall provide as follows:
"Notwithstanding anything contained in this article or elsewhere in this code, any feeder or branch feeder circuit of less than fifty (50) amperes shall use copper rather than aluminum wire."
(Ord. 06-822, 3-14-2006)