All electrical service conductors shall be installed according to the National Electrical Code with the following additional requirements. The point of entrance in all cases shall be determined by the Grand Island Utilities Department:
Overhead Service. The service mast must be Rigid or Intermediate metal conduit. Where the service mast is used for the sole support of the service drop, the minimum size shall be two-inch. The service mast shall be continuous with no interruptions. The point of attachment shall be a minimum height of twelve (12) feet.
Underground Service. The service conductors shall be installed in a continuous approved conduit system from the service head, transformer or secondary tap box to the main meter socket or service disconnect. The first ten feet of conduit out of the ground attaching to a utility pole shall be schedule 40 G.R.C. conduit.
(Amended by Ordinance No. 9578, effective 03-29-2016) (Amended by Ordinance No. 9804, effective 01-01-2021)