8-3   International Building Code (IBC) And International Residential Code (IRC);
Standards Adopted
The following standards shall be used with the International Building Code and the International Residential Code adopted by §8-1 and §8-2 above:
Acceptable Wind Load Design Procedures:
2021 I.B.C. - The Basic Design Wind Speed shall be 125 mph, in risk category II,III,&IV. Exposure C only
2021 IRC – The Ultimate Design Wind Speed shall be 114 mph, Exposure C only.
Roof Snow Load - 30 pounds per sq. ft. no reductions allowed Frost Depth - 36 inch minimum
Seismic Design Category A, Site Class D
IRC, Table R301.5 Amend live load for sleeping rooms from 30 pounds to 40 pounds per square foot.
(Amended by Ordinance No. 8955, effective 03-31-2005) (Amended by Ordinance No. 9162, effective 05-01-2008) (Amended by Ordinance No. 9475, effective 04-15-2014) (Amended by Ordinance No. 9661, effective 01-01-2018) (Amended by Ordinance No. 9802, effective 01-01-2021)
HISTORY
Amended by Ord. 9958 on 12/20/2023