(A) General. The following provisions shall further apply and shall supersede any and all references listed within the adopted Edition of the National Electrical Code - 2005 Edition - NFPA No. 70.
(B) Additions, insertions and changes.
(1) Article 210.12 Arc-fault Circuit- Interrupter Protection - Delete entire section.
(2) Article 230.43 Wiring methods - Delete the following:
(1) Open wiring on insulators
(2) Type IGS Cable
(6) Electric nonmetallic tubing (ENT)
(7) Service-entrance cable
(8) Wireways
(9) Busways
(10) Auxiliary gutters
(11) Rigid nonmetallic conduit
(12) Cablebus
(13) TypeNC Cable
(14) Mineral-insulated, metal sheathed cable
(15) Flexible metal conduit
(16) Liquid-tight flexible nonmetallic conduit
(3) Article 310.2(B) - Delete “aluminum, copper-clad aluminum, or”.
(4) Article 314.1 add the following: All boxes installed at a conductor splice point, outlet, switch point, junction point or pull point shall be a Minimum of 4 x 4-1/2 inch steel Exception - ceiling fan boxes.
(5) 334.10 Type NM, NMC, and NMS shall be approved for single-family homes only.
(6) 334.15 (D) Type NM and NMC shall not be permitted to be exposed except in unfinished attics, and under-floor spaces.
(7) 334.40 (D) add the following: When type NM or NMC is used, a 12 inch loop shall be left before entering a box or device.
(8) 362 Electric non-metallic tubing: delete the section in its entirety.
(9) 394 Knob-and-tube wiring: delete the section in its entirety.
(Ord. VG09-008, passed 9-30-2009)