1046.28   TEMPORARY SERVICE FOR CONSTRUCTION FROM UNDERGROUND FACILITIES (120/240 V SINGLE-PHASE).
   (a)   Applicant's Responsibilities. The applicant shall:
      (1)   Apply for service at the office of the Electric Department or such other location as is from time to time designated by Council;
      (2)   Supply and install the following facilities at a location designated by a representative of the Electric Department (Location to be a maximum of twenty feet from underground secondary facilities):
         A.   Pole of four inches by four inches timber or portable electrical board structure
         B.   Disconnect switch
         C.   Eight-foot ground rod
         D.   Ground wire
         E.   Conduit riser
         F.   Meter base
      (3)   Install facilities according to the Borough's specifications which will be furnished to the applicant upon request;
      (4)   Excavate and backfill the cable trench (minimum depth of twenty-four inches) from the temporary structure to the customer's secondary facilities;
      (5)   File an application with an electrical inspection agency approved by the Borough.
   (b)   Borough's Responsibilities. The Borough shall:
      (1)   Designate the temporary facility location;
      (2)   Supply and install service cable;
      (3)   Make a service connection upon receipt of approval from the electrical inspection agency approved by the Borough.
   (c)   Exceptions. Any exceptions to the policy set forth in this section must be approved by the Borough Manager prior to installation.
   (d)   Charges. Charges for such services shall be established from time to time by resolution of Council.
(Ord. 2211. Passed 4-29-97.)