§ 50.22 SPRINKLER SYSTEMS.
   (A)   Construction specifications. Water pipes entering premises and used for fire protection only and connected with automatic sprinkler devices shall be supplied from a separate pipe having an independent connection with the main and shall be provided with an outside controlling valve and a meter type, design and size to be approved by the Village Board, all at the expense of the person using same, and shall be so constructed as to permit, in case of necessity, an uninterrupted flow of water. No person shall make a connection without first having received a permit for the installation based on approval of proper plans and specifications by the Village Board.
   (B)   Testing sprinkler systems. Whenever the owner of a sprinkler system desires to make a test thereof, he or she shall first notify the Village Clerk, in writing, to that effect at least 24 hours prior to the time of the test. All water used in connection with the test shall be measured and paid for by the owner of the sprinkler system.
(Prior Code, § 7-4B-8) Penalty, see § 50.99