CHAPTER 53:  FIRE PROTECTION AND SAFETY
Section
Flammable and Combustible Liquids
   53.01   Compliance with International Fire Code
   53.02   Location requirements for aboveground tanks
   53.03   Spill control
   53.04   Protection against vehicular collision
   53.05   Maintenance of area within any dike
   53.06   Tank piping system in contact with soil; protection from corrosion
   53.07   Delivery and dispensing operations to comply with International Fire Code; determining liquid level; equipment requirements
   53.08   Application to facilities constructed after July 1, 2016
   53.09   Limitations as to tank capacity
FLAMMABLE AND COMBUSTIBLE LIQUIDS
§ 53.01 COMPLIANCE WITH INTERNATIONAL FIRE CODE.
   Except as otherwise provided in SDCL Chapter 34-38, aboveground storage tanks shall comply with the applicable provisions of Chapter 57 of the International Fire Code, 2015 edition.
(SDCL §  34-38-26)
§ 53.02  LOCATION REQUIREMENTS FOR ABOVEGROUND TANKS.
   (A)   Any aboveground storage tank shall be located at least:
      (1)   Fifty feet from the nearest important building on the same property;
      (2)   Fifty feet from any fuel dispenser;
      (3)   Fifty feet from the nearest side of any public way; and
      (4)   Fifty feet from any property line that is or may be built upon.
   (B)   However, distances may be reduced based on site limitations and conditions or quantity of liquid storage at the discretion of the local and division authority having jurisdiction.
(SDCL § 34-38-28)
§ 53.03  SPILL CONTROL.
   Spill control shall be provided in accordance with Chapter 57 of the International Fire Code, 2015 edition.
(SDCL § 34-38-29)