(A) Booster pumps shall not be installed without the written approval of the town.
(B) In all booster pump installations, the suction of the pump shall be connected to an atmospheric tank, with the public water supply entering the tank being controlled by an automatic float valve and freely discharging into the tank a minimum of six inches above the positive overflow level of the tank.
(C) As an alternative, an approved backflow prevention device may be installed on the suction of the pump. The backflow preventer must meet the state’ Board of Health and Department of Environmental Management guidelines and must be tested and maintained as per state guidelines, with copies of test results submitted to the Superintendent of Water.
(D) A set of plans and specification must be submitted to the town, the state’s Board of Health and the Department of Environmental Management, as required, for approval before the installation of any booster pump.
(Prior Code, § 104.20) Penalty, see § 52.999