The retail sale of liquefied petroleum gases accessory to and on the same lot as an allowed use shall comply with all of the following requirements.
(1) In a C1 District, the sale of liquefied petroleum gases may be made only by the purchase of full containers or by the exchange of empty containers for full containers, the containers may not be filled onsite, and no liquefied petroleum gases may be stored on the lot other than in the containers available for purchase or exchange.
(2) In commercial districts other than a C1 District:
(i) the facility shall be located on a lot of at least 20,000 square feet;
(ii) only one storage tank is allowed and the capacity of the tank may not have a water capacity of more than 2,000 gallons;
(iii) the storage tank shall be at least 25 feet from all lot lines, 25 feet from any inhabitable structure if the tank has a water capacity of more than 500 gallons, and 10 feet from any inhabitable structure if the tank has a water capacity of less than 500 gallons;
(iv) steel or iron poles at least four inches in diameter and four feet above the ground shall be set in and filled with concrete not more than three feet apart around the perimeter of the tank at a distance from the tank equal to the height of the poles plus six inches;
(v) a chain link fence at least six feet high shall be provided with an access gate at both ends of the tank; and
(vi) an emergency telephone number for the gas company servicing the tank shall be posted in plain view on the tank site and in the onsite offices where the tank is located.
(Bill No. 4-05; Bill No. 78-05; Bill No. 2-09; Bill No. 15-12; Bill No. 8-15; Bill No. 44-15; Bill No. 96-15; Bill No. 75-16; Bill No. 83-16; Bill No. 17-17; Bill No. 67-17; Bill No. 16-20; Bill No. 68-20; Bill No. 69-20; Bill No. 90-20; Bill No. 2-21; Bill No. 103-21; Bill No. 81-22; Bill No. 15-23; Bill No. 62-23; Bill No. 77-23; Bill No. 3-24)