1113.07 CONSTRUCTION PLANS, WATER MAINS.
   (a)    All materials used and the installation of those materials shall be in accordance with City specifications, Chapter 1115.
   (b)    Fire hydrants shall be placed at a maximum of 500 foot intervals.
   (c)    Unless excepted by the City Engineer, there shall be four control valves at each cross-intersection and three control valves at each tee-intersection, also a valve ahead of each fire hydrant installation.
   (d)    Water mains shall be located eighteen feet from the center line of the street or as directed by the Commission. Dead ends will not be permitted.
   Where it is possible, a closed circuit to proposed or existing mains shall be obtained.
   All hydrants, plugs, caps, ties and bends deflecting twenty-two and one-half degrees or more on mains eight inches or larger in diameter shall be provided with concrete reaction backing which shall be of suitable design and the details shown on the drawings.
   (e)    The size of water mains to be installed in the new system will be determined by the City.
   (f)    All water service branches from the water mains to the houses will be installed in accordance with the rules and regulations of the Division of Water.
   (g)    The waterline system shall comply with City Standards for Waterline Details, Appendix A.
(Ord. 69-35. Passed 10-27-69.)