(A)
The total gasoline storage capacity of each filling or service or gasoline or motor supply station established 10-5-1970 shall be limited by the location of the storage tanks in respect to adjacent buildings which are not an essential part of the installation and adjacent lot lines as provided in the following table:
Capacity of Outside Underground Gasoline Storage Tanks | |
Fire Separation in Feet | Quantity of Storage in Gallons |
Capacity of Outside Underground Gasoline Storage Tanks | |
Fire Separation in Feet | Quantity of Storage in Gallons |
50 | Unlimited |
40 | 50,000 |
30 | 20,000 |
25 | 12,000 |
20 | 6,000 |
10 | 3,000 |
(B) Such station shall have no more than six pumps.
(Prior Code, § 15-2)