1313.02 FIRE HYDRANTS.
   Fire hydrants shall be installed at a rate of one for every 1,000 feet of street or fraction thereof when the fraction exceeds 500 feet, such hydrants shall be capable of producing 500 gallons per minute with 20 pound per square inch residual pressure. However, such hydrant shall be installed within 1,000 feet of adjacent hydrants, and no hydrant shall be closer than 500 feet to another hydrant. Location of such hydrants shall be approved by the fire chief.
(Ord. 2005-06-02. Passed 3-20-06.)