9-1D-1: ELECTRICAL CODE ADOPTED:
   A.   Adoption: Pursuant to the authority granted by chapter 65 Illinois Compiled Statutes 5/1-3-2, the Village of West Dundee hereby adopts by reference, as criteria for the issuance of construction, reconstruction, alteration, repair and installation permits the provisions of the published 2020 NEC with the following amendments:
   Article 210.8 Ground-Fault Circuit-Interrupter Protection for Personnel
      Add article 210.8(A)(11) All lights located within the enclosure of a shower or tub.
   Create Section 320.104(A) AC Cable run from a switch to a ceiling mounted box, capable of ceiling mounted fan installation, shall contain a minimum of 3 insulated conductors of a type listed in Table 310.104 or those identified for use in this cable.
   Create Section 330.104(A) MC Cable run from a switch to a ceiling mounted box, capable of ceiling mounted fan installation, shall contain a minimum of 3 insulated conductors of a type listed in Table 310.104 or those identified for use in this cable.
   Article 338 Service Entrance Cable: Type SE and USE
      Delete: Entire Article and any additional references in code.
   Article 340 Underground Feeder and Branch-circuit Cable: Type UF
      Delete: Entire Article and any additional references in code.
   Article 362 Electrical Nonmetallic Tubing: Type ENT
      Delete: Entire Article and any additional references in code.
   Create Article 408.54(A) Split Breakers. The use of split breakers used to increase the number of available over current devices shall be prohibited.
(Ord. 2017-15, 5-22-2017; amd. Ord. 2023-19, 8-21-2023)