§ 17.37 HEATING FACILITIES.
   (A)   Facilities required. Heating facilities shall be provided in structures as required by this section.
   (B)   Residential occupancies. Dwellings shall be provided with heating facilities capable of maintaining a room temperature of 68°F (20°C) in all habitable rooms, bathrooms and toilet rooms based on the winter outdoor design temperature for the locality indicated in the state’s Plumbing Code. Cooking appliances shall not be used, nor shall portable unvented fuel burning space heaters be used, as a means to provide required heating.
   (C)   Exception. In areas where the average monthly temperature is above 30°F (-1°C), a minimum temperature of 65°F (18°C) shall be maintained.
   (D)   Heat supply. Every owner and operator of any building who rents, leases or lets one or more dwelling units or sleeping units on terms, either expressed or implied, to furnish heat to the occupants thereof shall supply heat during the period from September 1 to June 1 to maintain a minimum temperature of 68°F (20°C) in all habitable rooms, bathrooms and toilet rooms.
   (E)   Exceptions.
      (1)   When the outdoor temperature is below the winter outdoor design temperature for the locality, maintenance of the minimum room temperature shall not be required provided that the heating system is operating at its full design capacity. The winter outdoor design temperature for the locality shall be as indicated in the state’s Plumbing Code.
      (2)   In areas where the average monthly temperature is above 30°F (-1°C), a minimum temperature of 65°F (18°C) shall be maintained.
   (F)   Occupiable work spaces. Indoor occupiable work spaces shall be supplied with a heat source during the period from September 1 to June 1 that is capable of maintaining a minimum temperature of 65°F (18°C) during the period the spaces are occupied.
   (G)   Exceptions.
      (1)   Processing, storage and operation areas that require cooling or special temperature conditions; and
      (2)   Areas in which persons are primarily engaged in vigorous physical activities.
   (H)   Room temperature measurement. The required room temperatures shall be measured three feet (914 mm) above the floor near the center of the room and two feet (610 mm) inward from the center of each exterior wall.
(Adopted 10-11-2016)