§ 153.55 BELOW GRADE CRAWLSPACES.
   (A)   The building must be designed and adequately anchored to resist flotation, collapse, and lateral movement of the structure resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy. Hydrostatic loads and the effects of buoyancy can usually be addressed through the required openings stated in division (B) below. Because of hydrodynamic loads, crawlspace construction is not recommended in areas with flood velocities greater than five feet per second unless the design is reviewed by a qualified design professional, such as a registered architect or professional engineer. Other types of foundations are recommended for these areas.
   (B)   The crawlspace is an enclosed area below the base flood elevation and, as such, must have openings that equalize hydrostatic pressures by allowing the automatic entry and exit of flood waters. The bottom of each flood vent opening can be no more than one foot above the lowest adjacent exterior grade.
   (C)   Portions of the building below the BFE must be constructed with materials resistant to flood damage. This includes not only the foundation walls of the crawlspace used to elevate the building, but also any joists, insulation, or other materials that extend below the BFE. The recommended construction practice is to elevate the bottom of joists and all insulation above BFE.
   (D)   Any building utility systems within the crawlspace must be elevated above BFE or designed so that flood waters cannot enter or accumulate within the system components during flood conditions. Ductwork, in particular, must either be placed above the BFE or sealed from flood waters.
   (E)   The interior grade of a crawlspace below the BFE must not be more than two feet below the lowest adjacent exterior grade.
   (F)   The height of the below-grade crawlspace, measured from the interior grade of the crawlspace to the bottom of the structural support of the next higher floor must not exceed four feet at any point.
   (G)   There must be an adequate drainage system that removes flood waters from the interior area of the crawlspace. The enclosed area should be drained within a reasonable time after a flood event. The type of drainage system will vary because of the site gradient and other drainage characteristics, such as soil types. Possible options include natural drainage through porous, well-drained soils and drainage systems such as perforated pipes, drainage tiles, or gravel or crushed stone drainage by gravity or mechanical means.
   (H)   The velocity of flood waters at the site should not exceed five feet per second for any crawlspace. For velocities in excess of five feet per second, other foundation types should be used.
(Ord. 527, passed 1-14-2013)