§ 52.017 LOCAL LIMITS.
   (A)   To implement the general and specific discharge prohibitions listed in this chapter, Industrial User-specific local limits have been developed ensuring that the POTW’s maximum allowable headworks loading is not exceeded for particular pollutants of concern for each Industrial User. Where specific local limits are not contained for a given parameter or pollutant in an Industrial User permit, the following limits will apply to all Users:
      0.003   mg/l   arsenic
      0.003   mg/l   cadmium
      0.061   mg/l   copper
      0.010   mg/l   cyanide
      0.049   mg/l   lead
      0.0003   mg/l   mercury
      0.021   mg/l   nickel
      0.005   mg/l   silver
      0.025   mg/l   total chromium
      0.175   mg/l   zinc
      16.0   mg/l   nitrogen ammonia
   (B)   Domestic sewage levels for pollutants not listed above shall be determined by the Director and shall be based on either actually measured local domestic sewage levels or literature values.
(Ord. passed 5-6-96) Penalty, see § 52.999