§ 154.052 DESIGN METHODOLOGY; DESIGN STORM.
   Public storm sewer pipes shall be designed to carry peak flows as determined by the methods previously described herein. All storm sewers shall be designed for the ten-year storm event. The 100-year storm shall be used as a check storm to confirm storm water containment at levels below the rim opening to prevent surcharging. Manning’s Equation shall be used to calculate pipe flow and velocity. A listing of the Manning’s Equation roughness coefficients for various pipe materials may be found in the Kentucky Department of Highways Design Manual or the Louisville Metropolitan Sewer District Design Manual.