939.06 MINIMUM SIZE OF MAINS.
   (a)   To insure an adequate water supply for fire protection in the Village of Sheffield, no person shall install any water main that is less than eight inches in diameter on a public or private street in the Village of Sheffield. This has been a long standing policy in the approval process in regards to subdivisions.
   (b)   Distance between fire hydrants shall be determined by the Service Department and the Village Engineer, but in no case shall such distance be greater than 500 feet.
(Ord. 1116. Passed 2-12-90.)