§ 23-4-14 BACKFLOW PREVENTION DEVICE; CONDITIONS WHERE REQUIRED.
   An approved backflow prevention device shall be installed when the following conditions are found by the City Manager to exist:
   (A)   Where a substance is handled in such a fashion as to create an actual or potential hazard to a public water supply system. This shall include premises having sources or systems containing process fluids or waters originating from a public water supply system which are no longer under the sanitary control of the city;
   (B)   Where internal cross-connections are not correctable in the judgment of the City Manager, or there exists intricate plumbing arrangements which make it impracticable to determine whether or not cross-connections exist;
   (C)   Where, because of security requirements or other prohibitions or restrictions, it is impossible or impractical to make a complete cross-connection survey;
   (D)   Where cross-connections have been established or re-established within the preceding three years; or
   (E)   Where there is more than one customer service connection which could constitute a potential cross-connection.
(Ord. 3261, passed - -1992)