1357.30 BUILDING SEWER SIZE.
   (a)   Required Size. The size of the building sewer shall be determined in accordance with the Ohio Plumbing Code.
   (b)   Installation. Building sewers shall be installed at a uniform slope of not less than one-fourth inch per foot and may be reduced to one-eighth inch per foot in accordance with the Ohio Plumbing Code toward the point of disposal and shall be laid on a firm bed of approved materials. Cleanouts shall be placed at the junction of the building drain and building sewer and at intervals not to exceed 100 feet in straight runs.
(Ord. 92-070. Passed 6-8-92.)