Chapter 7
SANITARY DRAINAGE
Part I – DRAINAGE SYSTEMS
SECTION 701.0 – GENERAL
701.2(2)(a)  Revise this section as follows:
701.2(2)(a)  ABS and PVC installations are limited to not more than two stories of commercial or privateresidential accommodations.
701.2(3)  Revise this section as follows:
701.2(3)  No vitrified clay pipe or fittings shall be used above-ground or where pressurized by a pump or ejector or underground within the foundation line of the building. They shall be kept not less than 12 inches (305 mm) belowground.
701.2(7)  Add the following section:
701.2(7)  Copper tubing shall not be used for urinal drainage or applications which are detrimental to the integrity of copper tubing.