Fire pumps and associated equipment shall be located in a separate two-hour fire resistive room. There shall be no other equipment in the room.
A. Location of the fire pumps, diesel fuel tanks, and controls shall be approved by the authority having jurisdiction prior to installation.
B. When a fire pump is located in a basement or other areas subjected to flooding, sump pump(s) shall be installed. Sump pumps shall be connected to the standby power system. The sump water level shall be monitored in the fire control room. A "trouble" signal shall be transmitted when water level rises above normal. (Prior code §§ 9.28.1274, 15.17.1702)