A graphic illustrated control panel for the smoke removal system shall be installed with the following controls and show the location of the following items:
A. Controls.
1. Fan control switches and indicator lights;
2. Damper control switches and indicator lights;
3. Stair pressurization fan controls and indicator lights.
B. Locations.
1. All smoke removal fans, duct work and area(s) served;
2. Stair pressurization fan(s) locations. (Prior code §§ 9.28.1228, 15.11.1109)