15.100.270   Annunciation panel graphics.
   In addition to the graphic illustration (elevation) an illustration of the ground floor shall be provided. The panel shall be of sufficient size to accommodate any control switches, visual displays, lettering and be clearly legible. This shall not be an annunciation device, but shall show the following items:
   A.   Location of stairway and/or corridor systems to the exterior of the building;
   B.   All elevator lobbies;
   C.   Location of the fire control room;
   D.   All hydrant locations within the area of the building;
   E.   Fire department standpipe connection locations;
   F.   CO2 system connection (when provided);
   G.   Piped air system inlet location;
   H.   Emergency generator and fire pump fuel fill location(s). (Prior code §§ 9.28.1226, 15.11.1107)