A. The fire alarm annunciator panel shall be a graphic illustration of the building elevation, and shall be of sufficient size to accommodate any control switches, visual displays, lettering and be clearly legible, and showing the following:
1. All floor levels to include below grade and helistop;
2. All stairways to include upper and lower terminus of each stair;
3. All elevator banks and floors served;
4. Fire equipment storage rooms;
5. Fire pump(s);
6. Generator(s).
B. In addition to the graphic illustration, the fire alarm annunciator panel shall visually display alarm, trouble and supervisory signals immediately adjacent to the floor, area or zone the devices are serving. When zones are divided, they shall be displayed separately.
Each zone shall display, but not be limited, to the following:
1. Every smoke detection zone;
2. Every duct detection zone;
3. Every water flow alarm/tamper zone;
4. Every manual pull station zone;
5. Every heat detection zone;
6. Any other fire extinguishing system. (Prior code §§ 9.28.1225, 15.11.1106)