8.48.130   Temporary fireworks stand.
   All retail sales of safe and sane fireworks shall be permitted only from within a temporary fireworks stand, and the sale from any other building or structure is prohibited. Temporary stands shall be subject to the following provisions:
   A.   No fireworks shall be located within 25 feet of any other building or within 100 feet of any gasoline pump or distribution point.
   B.   Fireworks stands need not comply with the provisions of the building code of the city; provided, however, that all stands shall be erected under the supervision of the inspector, who shall require that stands be constructed in a manner that will reasonably ensure the safety of attendants and patrons; and provided further that any electrical installations shall comply with all applicable codes.
   C.   No stand shall have a floor area in excess of 750 square feet.
   D.   Each stand shall have at least two exits. Each stand in excess of 40 feet in length shall have at least three exits spaced approximately equidistant apart; provided, however, that in no case shall the distance between exits exceed 20 feet. Exit doors shall be not less than 24 inches wide and 6 feet in height and shall swing in the direction of exit travel.
   E.   Each stand shall be provided with two, two and one-half gallon "water type" (minimum rating 2A) fire extinguishers in good working order and easily accessible for use in case of fire.
   F.   All temporary fireworks stands shall be disassembled and removed not later than July 20 of that year. (Ord. 2021-0019 § 5; Ord. 2003-030 § 6; prior code § 15.03.385)