Section BB105.1 of appendix BB of the California fire code is hereby amended by amending the exception to read as follows:
Exception: A reduction in required fire-flow of up to 50 percent (50%), is allowed when the building is provided with an approved automatic sprinkler system. When a reduction in fire flow is used, fire flow shall not be less than 1500 gpm.