15.20.680: APPENDIX B:
Section B105.2 of appendix B of the California fire code is hereby amended by amending the exception to read as follows:
   Exception: A reduction in required fire-flow of up to 50 percent (50%), as approved, is allowed when the building is provided with an approved automatic sprinkler system installed in accordance with section 903.3.1.1 or 903.3.1.2. The resulting fire-flow shall not be less than 1,500 gallons per minute (5678 l/min) for the prescribed duration as specified in table B105.1(2).
(Ord. 2948, 2022: Ord. 2900, 2019: Ord. 2840, 2016)