Section 507.5.7:
Section 509.3 of the California fire code is hereby added to read as follows:
509.3 Access to Equipment in Multi-Unit Buildings. When automatic fire sprinkler systems or fire alarm systems are installed in buildings constructed for multiple tenants and these systems protect multiple tenant spaces, the main controls and control appurtenances, such as risers, fire alarm control panels, and valves for such systems, shall be located in an attached or included room or an approved weather-resistant enclosure with at least one exterior access door of not less than 3'-0" by 6'-8".
(Ord. 2948, 2022: Ord. 2900, 2019: Ord. 2840, 2016)