15.20.240: FIRE HYDRANTS AND MAINS:
Section 507.5.1 of the California fire code is hereby amended to read as follows:
   507.5.1 Where Required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet (91 m) from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.
      Exceptions:
      1.   For group R-3 and group U occupancies, the distance requirement shall be 600 feet (183 m). This distance may be further modified by the fire code official for such occupancies when buildings are equipped throughout with an approved fire sprinkler system installed in accordance with section 903.3.1.3.
      2.   Deleted.
(Ord. 2948, 2022: Ord. 2900, 2019: Ord. 2840, 2016)