§ 97.03 DRILLING OR INSTALLATION OF OTHER FACILITIES WITHIN DESIGNATED DISTANCE FROM MUNICIPAL WATER SOURCES: PROHIBITED.
   Under no circumstances shall the City Council approve any permit to drill or operate any of the below described facilities within the indicated number of feet from any City of Ravenna municipal water well:
Category
Distance
Category
Distance
Non-potable water well
1,000 feet
Sewage lagoon
1,000 feet
Absorption or disposal field for waste
500 feet
Cesspool
500 feet
Dump
500 feet
Feedlot or feedlot runoff
500 feet
Corral
500 feet
Pit toilet
500 feet
Sanitary landfill
500 feet
Chemical or petroleum product storage
500 feet
Septic tank
500 feet
Sewage treatment plant
500 feet
Sewage wet well
500 feet
Sanitary sewer connection
100 feet
Sanitary sewer manhole
100 feet
Sanitary sewer line
100 feet
Sanitary sewer line (permanently water tight)
10 feet
 
(Ord. 2002-O-013, passed 7-5-02)