4-6-3: ADDITIONS, INSERTIONS AND CHANGES TO INTERNATIONAL FIRE CODE:
The following sections are hereby revised as follows:
Chapter 1
 
Paragraph 101.1:
 
Insert: City of Plano, Kendall County, Illinois
Paragraph 103.1:
 
Delete in its entirety (department of fire prevention already created).
Paragraph 103.2:
 
Delete in its entirety and insert:
Appointment. The Code Official of the City of Plano hereby appoints the Fire Chief of the Little Rock - Fox Fire Protection District as fire code official with the responsibility for the implementation, administration and enforcement of this code.
Paragraph 105.1:
 
Before the word "Permits", insert: "The Code Official of the City of Plano authorizes the Fire Chief of the Little Rock - Fox Fire Protection District to issue construction permits for work as set forth in Sections 105.1.1 through 105.7.25 and to charge appropriate fees for review and inspections as set forth in the Little Rock - Fox Fire Protection District's Fire Prevention Ordinance, #2003-01 and as amended from time to time.
Paragraph 110.4:
 
At line 7 insert: "Petty" and at line 8 insert the words: "not less than fifty five dollars ($55.00) nor more than five hundred dollars ($500.00) per offense." Delete the remainder of this sentence.
Paragraph 112.4:
 
Insert: At the first (amount) insert the words: "Fifty five dollars ($55.00)", at the second (amount) insert the words: "five hundred dollars ($500.00)". At the end of the paragraph, add the words: "For each day a violation continues."
Chapter 9
 
Section 901:
 
After paragraph 901.1, insert new paragraphs 901.1 A:
901.1.A. Fire Protection System Required: Effective from this date, in all Use Groups and Construction Types an automatic fire protection system shall be required when the gross building area exceeds twenty thousand (20,000) square feet, or unless Section 903 of this Code, or Table 506.2 of the 2018 International Building Code requires an automatic fire protection system at a smaller area.
Paragraph 903.2.8:
 
Insert:
a) Exception. An automatic sprinkler system is not required in single family and duplex structures in the R-3 Use Group.
Paragraph 904.12:
 
Insert: 904.12.6. All occupancies with a commercial cooking operation shall have a monitored fire alarm system in accordance with the applicable requirements of NFPA 70 and NFPA 72.
Paragraph 907.1:
 
Insert: 907.1.4. Provide a red colored lens visual device above the fire department connection that activates on water flow only. Provide a clear lens visual device above the entrance to each building that activates on all alarms. In multi-tenant buildings provide a clear lens visual device at the entrance to each tenant space, zone the device to that space.
Insert 907.1.5:
Combination fire and burglar alarm systems are prohibited in structures that contain automatic sprinkler systems.
Paragraph 1206.1:
 
Insert 1206.1.1. NFPA 855 2020 Standard for the Installation of Stationary Energy Storage Systems: Installation of Stationary Energy Storage Systems shall comply with this standard as applicable.
Chapter 56
 
Insert new paragraph after 5601.1:
5601.1.A. ESTABLISHMENT OF LIMITS OF DISTRICTS IN WHICH STORAGE OF EXPLOSIVES AND BLASTING AGENTS IS PROHIBITED. The storage of explosive and blasting agents is prohibited within the corporate limits of the City of Plano, except with special permit issued by The Little Rock - Fox Fire Protection District.
Insert new paragraph after paragraph 5601 A.:
5601.1.B. ESTABLISHMENT OF LIMITS OF DISTRICTS IN WHICH THE SALES, MANUFACTURING, AND STORAGE OF FIREWORKS IS PROHIBITED. The manufacturing, sale, handling, use or storage of fireworks is prohibited within the corporate limits of the City of Plano, except with special permit issued by the Little Rock - Fox Fire Protection District.
Insert the following new paragraph after paragraph 55609.1:
5610.1. ESTABLISHMENT OF MOTOR VEHICLE ROUTES FOR VEHICLES TRANSPORTING EXPLOSIVES OR BLASTING AGENTS. Vehicles transporting explosives or blasting agents are hereby prohibited within the corporate limits of the City of Plano, with the following exceptions:
a)   Route 34, (South Street)
b)   Burlington Northern Railroad
Insert new paragraph after 5610.1:
5610.2. ESTABLISHMENT OF LIMITS OF DISTRICTS IN WHICH THE STORAGE OF FLAMMABLE LIQUIDS IN OUTSIDE, ABOVE GROUND TANKS, IS PROHIBITED. The storage of flammable liquids in outside, above ground tanks is prohibited within the corporate limit of the City of Plano, except with special permit issued by the Little Rock -Fox Fire Protection District.
 
 
Insert new paragraph 5610.3 after paragraph 5610.2:
5610.3. ESTABLISHMENT OF MOTOR VEHICLE ROUTES FOR VEHICLES TRANSPORTING HAZARDOUS CHEMICALS OR OTHER HIGHLY TOXIC AND TOXIC MATERIALS. Vehicles transporting hazardous chemicals or other dangerous materials are prohibited within the corporate limits of the City of Plano, with the following exceptions:
a)   Route 34 (South Street)
b)   Burlington Northern Railroad
c)   Eldamain Road.
Chapter 61
 
Insert new paragraph after paragraph 6101.1. A.:
6101.1.A. ESTABLISHMENT OF LIMITS IN WHICH BULK STORAGE OF LIQUIFIED PETROLEUM GASES IS TO BE RESTRICTED. The above ground storage of five hundred (500) gallons total of all tanks is prohibited within the corporate limits of the City of Plano, except with special permit issued by the Little Rock - Fox Fire Protection District.
 
(Ord. 2020-9, 5-11-2020)