§ 155.687 NON-RESIDENTIAL LIGHTING STANDARDS.
   (A)   Light fixtures; types.
      (1)   Pole mounted light fixtures on nonresidential properties shall be full cutoff fixtures, and shall be incorporated as an integral design element that compliments the design of the building or project through style, material or color. Exception - non-cutoff fixtures for pedestrian scale lighting for walkways may be utilized for nonresidential projects upon review and approval of the Planning and Zoning Board. Planning and Zoning Board consideration may be with restrictions.
      (2)   Lighting of buildings shall be limited to wall washer type fixtures or up-lights, which do not produce spill light or glare. Sag lenses, convex lenses, and drop lenses shall be prohibited.
      (3)   Security lighting. Attached building fixtures, utilized for parking lot security purposes only, may be aimed no higher than 45 degrees above straight down.
      (4)   Time controls and dimmers. Nonresidential lighting shall be installed with time controls and dimmers which will assure that the required illumination shall be provided at dusk and that light levels are reduced not later than one hour by a minimum of 25% after the close of operations to the minimum levels needed to ensure safety and security.